Electromedia®
I Operating Characteristics
- Filter Rate: Up
to 18 gpm per sq. ft.
- Backwash Rate:
20 gpm per sq. ft.
- Required Backwash
Time: 4 minutes maximum.
- Clean Filter Differential
Pressure: 1 psi.
- Terminal Differential
Pressure: 10 psi.
Standard
Equipment
- Flow range from
10 to 10,500 gpm or more.
- 60 psi pressure
tank ASME code, stamped.
- Filter tanks are
carbon steel, epoxy lines at all wetted surfaces.
- Backwash flow controls,
air release valves, and automatic filter control valves provided
as standard.
- Standard interior
fittings: cast iron, PVC, and stainless steel.
- Each tank fitted
with 12" X16" manholes, 6" x 8" hand holes,
or manways depending on filter size.
Automation
- PLC based automatic
filter controls include automatic reset timers for filtration,
backwash and purge.
- Backwash is initiated
by time or differential pressure override.
- Controls housed
in a NEMA 12 enclosure.
Tank
Sizing Chart

|
|
CASE